Low-voltage busbar installation rules:.

1. low voltage. Handling and storage of bus ducts.

Busbars shall not be lifted and bundled with bare wire rope, stacked or dragged on the ground. No other operations shall be carried out on the enclosure. Multipoint lifting and shovelling shall be used without damaging the busbar. Bus ducts shall be stacked in a dry, clean warehouse free from corrosive gas contamination. Flexible packing gasket should be clamped between the upper and lower busbar conduits, and properly stored.

2. Installation trend of low voltage busway.

Each batch of busway shall be delivered with a trend diagram and a detailed set of trend tables. All bus ducts are numbered with the appropriate branch and section numbers and are numbered sequentially during installation.

3. Pre-installation busway inspection.

Check whether the busway shell is intact and damaged, check whether the busway shell bolts are loose, and make sure that the bolts are connected reliably; check whether the busway joints are closed and locked; measure the insulation resistance with a 500-volt megohmmeter, and the resistance value is not less than 20ω per section.

Busway maintenance.

Equipment with voltage can cause serious injury or death, so bus duct maintenance can only be carried out after cutting off the power supply.

1. check whether the connector connecting bolts and fixed bracket bolts are loose within 6 months after the bus duct is installed and used, carry out a comprehensive inspection after 1 year, and carry out a thorough internal and external inspection every 3 years.

2. Check that the total load current does not exceed the main bus duct current or design current, and check the operating temperature.

3. Check that the busbar system is not de-energised before busbar maintenance! Completely cut off all power supply to the bus duct! Measure the voltage of the conductor with a multimeter to confirm that the busbar system is not charging before routine maintenance. Prevent high voltage may lead to serious accidents of personal injury or even death of the operator!

4. During maintenance, use a soft brush, hoover or cotton cloth to clean dust from the busbar. During maintenance, pay special attention to the clamping torque and surface cleanliness of the connectors. If the structure is loose or contaminated, the use resistance will increase, overheating, and even unevenness of the connection surface may cause arcing phenomenon.

5. When the bus duct is in operation, check whether there are leaks, water sprays, potential moisture sources around the whole system, whether there are heavy objects threatening the system, whether there are heat sources affecting the temperature rise of the bus duct system, and check whether there are any foreign objects entering the bus duct.

6. Check the busway system components for defects and corrosion, and the bracket springs for proper elasticity, and replace them immediately if problems are found.

7. When the busway is running for a long time, the temperature rise of the joints should be tested regularly once a year, and the temperature rise of the joints should not exceed 70K according to GB7251 standard.

8. Check whether there is aging of insulating materials and whether there is melting and deformation of conductive parts. Phase-to-phase insulation breakdown, should be removed in sections, with a voltage tester section check to find out the fault, or re-replace the busway, or re-insulation coating treatment.

9. Check whether the plug-in box pins of the busbar trunking system are in good contact with the busbar.

10. Before supplying power to the busbar system again, check the insulation resistance and record it.

11. After maintenance to ensure that the busbar system of the original protection level requirements.

The above collation sums up the rules about Guangdong low-voltage busway installation, maintenance and maintenance methods, I hope to help you.